Greymetal supply Efficient contemporary wood burning stoves and multifuel stoves Greymetal supply Efficient contemporary wood burning stoves and multifuel stoves
 
 
 
 
 

Before the stove is first used, refer to the Stove Operation page on the website or the operation manual.

 
The below is a brief summary and is not intended to replace thorough reading of and strict adherence to all the relevant Building Regulations.
 
Stove Installation:
 
 
DIY installations must be carried out according to the guidelines laid out in Building Regulations Approved Document J, 2010:
 
 
Read all the relevant sections (0,1 and 2) and appendices thoroughly!
 
You must also inform the local Building Control office prior to installation.
 
 
Combustion Air requirement:
 
 
Stoves with a draught stabiliser fitted into the flue pipe, or stoves over 5kW will require a permanently open vent as per Building Regulations Table 1 Page 29 – “Other Appliances”.
 
An air vent in the wall near to the wood burner will prevent cold draughts travelling across the room and is highly recommended for all stoves.
 
Extractor fans must not be placed in the same room as the stove.
 
 
 
 
 
Hearth Suitability:
 
 
Building Regulations Approved Document J, Pages 37- 39, Diagrams 24-27.
 
Before installing the stove, you must ensure that the load-bearing capacity of the floor can withstand the weight of the stove plus flue pipe and connections.
 
Building Regulations Approved Document J, Pages 37- 39, Diagrams 24-27.
 
If the stove is placed on a combustible floor, the stove should always be installed on a non-combustible hearth. The hearth should extend 225mm in front of the stove and 150 mm to each side.
 
None of our products exceed 100ºc at hearth level. They may be placed on a 12mm non-constructional hearth directly onto the floor.
 
 
 
 
Distance of stove to adjacent walls, combustible, non-combustible:
 
The CE plate on the rear of the stove indicates the minimum distance to combustible surfaces to the back, sides, and to the front of the stove.
 
There is no requirement for minimum clearance to non-combustible surfaces around the sides and back of the stove. However, 80mm is recommended if possible to allow for air movement and heat from the stove to enter the room. The further the stove is into the room, the more heat distribution there will be into the room.
Refer to Diagram 30, Page 42 of Document J for further installation dimensions and requirements for non-combustible wall thickness etc.
 
Briefly:
·        There must be a minimum gap of at least 450mm (18'’) between any stove and any combustible material e.g. curtains, furniture.
·        If the stove is placed within 300mm of a wall, and sits on a hearth abutting a wall, then the wall must be non-combustible (usually brickwork or stone) to minimum heights of 300mm above the appliance and 1.2m above the hearth.
·        There is a minimum gap required between an un-insulated flue pipe and other material. To a combustible material it must be at least 3 x the outside diameter of the flue pipe (450mm for 6” single wall flue pipe). To a non-combustible shield it must be at least 1.5 x the flue diameter (225mm for 6” single wall flue pipe).
 
 
 
Some general points about Flue Pipes:
 
 
1.      Flue connections should be sealed with a suitable proprietary sealant such as fire cement or high temperature rope seal. Gunnable cartridge sealing compounds work well, and are easy to apply. We recommend and supply Fortafix Ceramix.
2.      If a suitable approved factory made system is to be used it should be installed to the manufacturer’s instructions.
3.      A Flue / chimney height of 4.5m should be adequate in most situations measured from the stove’s top air inlet to the top of the flue.
4.      No horizontal sections are allowable.
5.      Flues should have a maximum of 4 bends with angles of 45 degrees. And a maximum of two bends in-between each sweeping access point. [Page 27 Diagram 15].
6.      The flue exit from the building should be positioned to comply with the requirements of the Building Regulations. These can be seen on page 31 Diagram 17.
7.      If the chimney is too high (draught exceeds 35 Pa) or so that the chimney draught can be regulated on days with strong winds, it is necessary to fit the chimney or flue with a damper.
8.      No other heating appliances should be connected to the same Flue or Chimney system.
 
 
 
Finally:
 
1.      The Flue or Chimney must be unblocked, clean and sound (no leaks), and should be professionally inspected and swept before use.
2.      Check the flue draught. This should be done with all windows and doors closed and any extraction fans in adjoining rooms running at maximum speed.